Phases: 1
Output Current: 10 A
Mode: Primary-Switched
Output Voltage: 12 VDC
Type: DIN Rail Power Supply Unit
Power Supply Unit Products: Din Rail Power Supply Unit
Product Type: Power Supply Unit
  • Connection data, input
    Conductor cross section AWG/kcmil max: 14
    Conductor cross section AWG/kcmil min.: 24
    Conductor cross section solid max.: 2.5 mm²
    Conductor cross section solid min.: 0.2 mm²
    Conductor cross section stranded max.: 2.5 mm²
    Conductor cross section stranded min.: 0.2 mm²
    Connection method: Screw connection
    Screw thread: M2,5
    Stripping length: 9 mm
  • Connection data, output
    Conductor cross section AWG/kcmil max: 14
    Conductor cross section AWG/kcmil min.: 24
    Conductor cross section solid max.: 2.5 mm²
    Conductor cross section solid min.: 0.2 mm²
    Conductor cross section stranded max.: 2.5 mm²
    Conductor cross section stranded min.: 0.2 mm²
    Connection method: Screw connection
    Stripping length: 9 mm
  • General data
    Ambient temperature (operation): -25 °C ... 70 °C (> 55° C derating)
    Ambient temperature (storage/transport): -40 °C ... 85 °C
    Assembly instructions: Can be aligned: Horizontally 0 mm, vertically 50 mm
    Degree of protection: IP20
    Depth: 115 mm
    Efficiency: > 86 % (for 230 V AC and nominal values)
    Electromagnetic compatibility: Conformance with EMC Directive 2004/108/EC
    Height: 130 mm
    Insulation voltage input/output: 4 kV AC (type test)
    Insulation voltage input/output: 2 kV AC (routine test)
    Low Voltage Directive: Conformance with LV directive 2006/95/EC
    Max. permissible relative humidity (operation): ? 95 % (at 25 °C, no condensation)
    Mounting position: horizontal DIN rail NS 35, EN 60715
    MTBF (IEC 61709, SN 29500): > 500000 h
    Net weight: 0.6 kg
    Noise immunity: EN 61000-6-2:2005
    Operating voltage display: Green LED
    Protection class: I, with PE connection
    Standard - Electrical safety: EN 60950-1/VDE 0805 (SELV)
    Standard - Electrical safety: EN 61558-2-17
    Standard - Safe isolation: DIN VDE 0100-410
    Standard - Safe isolation: DIN VDE 0106-1010
    Standard - Safety of transformers: EN 61558-2-17
    Standard ? Electrical equipment of machines: EN 60204
    Standard ? Electronic equipment for use in electrical power installations and their assembly into electrical power installations: EN 50178/VDE 0160 (PELV)
    Standard ? Limitation of mains harmonic currents: EN 61000-3-2
    Standard ? Protection against electric shock: DIN 57100-410
    Standard ? Protection against shock currents, basic requirements for protective separation in electrical equipment: DIN VDE 0106-101
    Standard ? Safety extra-low voltage: EN 60950-1 (SELV)
    Standard ? Safety extra-low voltage: EN 60204 (PELV)
    Surge voltage category: III
    UL approvals: UL/C-UL listed UL 508
    UL approvals: UL/C-UL Recognized UL 60950
    Width: 40 mm
  • Input data
    AC frequency range: 45 Hz ... 65 Hz
    AC input voltage range: 85 V AC ... 264 V AC (derating < 90 V AC: 2.5% per Kelvin)
    Current consumption: Approx. 1.7 A (120 V AC)
    Current consumption: Approx. 0.9 A (230 V AC)
    Inrush surge current: < 15 A
    Nominal input voltage: 100 V AC ... 240 V AC
    Nominal power consumption: (> 12 V constant capacity)
    Power failure bypass: > 20 ms (120 V AC)
    Power failure bypass: > 86 ms (230 V AC)
    Protective circuit/component: Varistor
    Recommended backup fuse: B6
    Recommended backup fuse: B10
    Recommended backup fuse: B16
    Short-term input voltage: 300 V AC
    Type of protection: Transient surge protection
  • Output data
    Note on status display: U<sub>OUT</sub> < 0.9 x U<sub>N</sub>: LED flashing
    Status display: "DC OK" LED green
  • Signaling
    Connection in parallel: Yes, for redundancy and increased capacity
    Connection in series: Yes
    Control deviation: < 1 % (change in load, static 10% ... 90%)
    Control deviation: < 2 % (change in load, dynamic 10% ... 90%)
    Control deviation: < 0.1 % (change in input voltage ±10%)
    Current limitation: Approx. 12 A (in the event of a short-circuit)
    Derating: 55 °C ... 70 °C (2.5%/K)
    Max. capacitive load: Unlimited
    Maximum power dissipation NO-Load: 1.1 W
    Nominal output voltage: 12 V DC ±1%
    Output current: 10 A (-25°C ... 55°C)
    Peak switching voltages nominal load: < 70 mV<sub>PP</sub>
    Power loss nominal load max.: 18 W
    Residual ripple: < 20 mV<sub>PP</sub>
    Setting range of the output voltage: 10 V DC ... 18 V DC (> 12 V constant capacity)