Menu

2856032 - Phoenix Contact Connector

Surge protection connector PT protective connector with protective circuit for a 2-wire floating signal circuit. HART-compatible.


Part #: 2856032
$171.00Add to Cart
Availability :
Backordered

Phoenix Contact Connector

Connector Type: Surge Protection
Includes: Protective Circuit
Type: HART-Compatible
Connection: PT Protective Connector
Product Type: Connector
  • Connection, protective circuit
    Standards/regulations: IEC 61643-21
    Standards/regulations: DIN EN 61643-21
    Standards/regulations: UL 497B
  • General
    Ambient temperature (operation): -40 °C ... 85 °C
    Arrester can be tested with CHECKMASTER from software version:: From SW rev. 1.00
    Color: black
    Degree of protection: IP20
    Depth: 52 mm
    Design: DIN rail module, two-section, divisible
    Direction of action: Line-Line & Line-Signal Ground/Shield & optional Signal Ground/Shield-Earth Ground
    Height: 45 mm
    Housing material: PA 6.6
    Inflammability class according to UL 94: V0
    Mounting type: On base element
    Pitch unit: 1 Div.
    Standards for air and creepage distances: VDE 0110-1
    Standards for air and creepage distances: IEC 60664-1
    Total surge current (8/20) µs: 20 kA
    Width: 17.7 mm
  • Protective circuit
    Capacity (Core-Core): 1.4 nF
    Cut-off frequency fg (3 dB), sym. in 50 Ohm system: Typ. 6 MHz
    Ground conductor current I<sub>PE</sub>: ? 2 µA (Directly grounded)
    Ground conductor current I<sub>PE</sub>: ? 1 µA (BE: 1x2+F)
    IEC category: C1
    IEC category: C2
    IEC category: C3
    IEC category: D1
    Input attenuation aE, sym.: 0.5 dB (? 1 MHz)
    Input attenuation aE, sym.: 0.5 dB (? 1 MHz / 50 ?)
    Lightning test current (10/350) µs, peak value l<sub>imp</sub>: 2.5 kA
    Max. discharge surge current Imax (8/20) µs maximum (Core-Core): 10 kA
    Max. discharge surge current Imax (8/20) µs maximum (Core-Earth): 10 kA
    Max. required back-up fuse: 500 mA (e.g. T ( IEC 127-2/III))
    Maximum continuous operating voltage U<sub>C</sub>: 28 V DC
    Maximum continuous operating voltage U<sub>C</sub>: 20 V AC
    Maximum continuous voltage U<sub>C</sub> (wire-ground): 20 V AC
    Maximum continuous voltage UC (wire-wire): 28 V DC
    Nominal current I<sub>N</sub>: 450 mA (45°C)
    Nominal discharge surge current I<sub>n</sub> (8/20) µs (Core-Core): 10 kA
    Nominal discharge surge current I<sub>n</sub> (8/20) µs (Core-Earth): 10 kA
    Nominal pulse current Ian (10/1000) µs (Core-Core): 30 A
    Nominal voltage U<sub>N</sub>: 24 V DC
    Operating effective current I<sub>C</sub> at U<sub>C</sub>: ? 5 µA
    Output voltage limitation at 1 kV/µs (Core-Core) spike: ? 40 V
    Output voltage limitation at 1 kV/µs (Core-Core) static: ? 40 V
    Output voltage limitation at 1 kV/µs (Core-Earth) spike: ? 450 V
    Output voltage limitation at 1 kV/µs (Core-Earth) spike: ? 1 kV (BE: 1x2+F)
    Protection level U<sub>P</sub> (Core-Core): ? 70 V
    Protection level U<sub>P</sub> (Core-Earth): ? 450 V
    Residual voltage at I<sub>n</sub>, (conductor-conductor): ? 40 V
    Residual voltage with Ian (10/1000)µs (conductor-conductor): ? 50 V
    Resistance in series: 2.2 ? (1-2/5-6/7-8/11-12)
    Response time tA (Core-Core): ? 1 ns
    Response time tA (Core-Earth): ? 100 ns
    Surge carrying capacity in acc. with IEC 61643-21 (Core-Core): C2 (10 kV/5 kA)
    Surge carrying capacity in acc. with IEC 61643-21 (Core-Earth): C2 (10 kV/5 kA)
    Surge carrying capacity in acc. with IEC 61643-21 (Core-Earth): D1 (2.5 kA)
    Total surge current (8/20) µs: 20 kA
    VDE requirement class: C1
    VDE requirement class: C2
    VDE requirement class: C3
    VDE requirement class: D1
Email this page to a friend
Part Number Tags: N/A

This part number has been discontinued by {Manufacturer}. Use the contact form below to find out the new compatible part.

Updating...