2804490
-
Phoenix Contact Surge Protection Device
Type 2 surge protection device Surge arrester for 2-pos. without fuse grounded DC voltage systems 1000 V DC, for DIN rail mounting, 2-pos. base element (L+, L-, ground) with remote indication contact, three pluggable temperature-monitored varistors, status message on each connector.
Part #: 2804490
Phoenix Contact Surge Protection Device
Color:
|
Black |
Material:
|
PBT, PA |
Connecting Thread:
|
M5 |
Type:
|
2, DIN Rail Module |
Positions:
|
2 |
Protection Level:
|
IP20 |
Nominal Voltage:
|
1000 VDC |
Connection:
|
Screw Connection, Biconnect Terminal Block |
Product Type:
|
Surge Protection Device |
- Protective circuit
Arrester rated voltage U<sub>C</sub>: 1000 V DC
EN type: T2
Ground conductor current I<sub>PE</sub>: ? 20 µA
IEC category: II
Max. discharge surge current Imax (8/20) µs: 30 kA
Nominal discharge surge current I<sub>n</sub> (8/20) µs: 15 kA
Nominal load current I<sub>L</sub>: ? 80 A DC
Nominal voltage U<sub>N</sub>: 1000 V DC (Non-load voltage U<sub>OC</sub>)
Protection level U<sub>p</sub>: ? 5 kV
Protection level Up (L+) - (L-): ? 5 kV
Residual voltage: ? 5 kV
Residual voltage: ? 4.5 kV (at 10 kA)
Residual voltage: ? 4 kV (at 5 kA)
Residual voltage (L+) - (L-): ? 5 kV
Residual voltage (L+) - (L-): ? 4.5 kV (at 10 kA)
Residual voltage (L+) - (L-): ? 4 kV (at 5 kA)
Response time: ? 25 ns
Standby power consumption P<sub>C</sub>: ? 20 mW
- Remote indicator contact
AWG conductor cross section: 30 ... 14 (UL)
Conductor cross section AWG/kcmil max: 16
Conductor cross section AWG/kcmil min.: 28
Conductor cross section solid max.: 1.5 mm²
Conductor cross section solid min.: 0.14 mm²
Conductor cross section stranded max.: 1.5 mm²
Conductor cross section stranded max.: 1.5 mm²
Conductor cross section stranded min.: 0.14 mm²
Conductor cross section stranded min.: 0.14 mm²
Connection method: MC 1,5/3
Connection method: MC 1,5/3
Max. operating current I<sub>max</sub>: 1.5 A AC (250 V AC)
Max. operating current I<sub>max</sub>: 1.5 A DC (30 V DC)
Maximum operating voltage U<sub>max.</sub> AC: 250 V AC
Screw thread: M2
Screw thread: M2
Stripping length: 7 mm
Stripping length: 7 mm
Switching function: PDT, 1-pos.
Switching function: PDT, 1-pos.
Tightening torque: 0.25 Nm
Tightening torque: 4 lb in (UL)
Tightening torque: 0.25 Nm
Tightening torque: 4 lb in (UL)
- Standards
Ambient temperature (operation): -40 °C ... 80 °C
Color: black
Degree of protection: IP20
Depth: 65.5 mm
Design: DIN rail module, two-section, divisible
Direction of action: (L+)-(L-)
Height: 99 mm
Housing material: PBT / PA
Inflammability class according to UL 94: V0
Message: Surge protection fault: Optical, remote indicator contact
Mounting type: DIN rail: 35 mm
Number of positions: 2
Pitch unit: 2 Div.
Standards for air and creepage distances: DIN EN 60664-1
Standards for air and creepage distances: DIN EN 61643-11
Standards/regulations: DIN EN 61643-11 2002
Standards/regulations: IEC 61643-1 2005
Standards/regulations: IEC 60364-7-712 2002
Width: 35.6 mm