Color: Nickel
Material: Brass
Nominal Current: 5 A
Protection Level: IP68
Type: Attachment Plug
Includes: Lambda/4 Technology
Connection: N Male/Female Connectors
Product Type: Surge Protection Device
  • Connection data
    Connection method: N Connector
    Connection type IN: N connector, male
    Connection type OUT: N connector, female
  • Connection, protective circuit
    Standards/regulations: IEC 61643-21
  • General
    Ambient temperature (operation): -40 °C ... 90 °C
    Color: nickel
    Degree of protection: IP68
    Depth: 89 mm
    Design: Attachment plug
    Direction of action: Line-Shield/Earth Ground
    Height: 66 mm
    Housing material: Brass (CuZn)
    Mounting type: Connection-specific intermediate plugging
    Total surge current (10/350) µs: 20 kA
    Total surge current (8/20) µs: 60 kA
    Width: 26.1 mm
  • Protective circuit
    Frequency range: 0.82 GHz ... 2.2 GHz
    IEC category: C2
    IEC category: C3
    IEC category: D1
    Input attenuation aE, asym.: Typ. 0.05 dB (? 0.15 dB)
    Lightning test current (10/350) µs, peak value l<sub>imp</sub>: ? 20 kA
    Max. discharge surge current Imax (8/20) µs maximum (Core-Earth): 60 kA
    Max. discharge surge current Imax (8/20) µs maximum (Core-Shield): 60 kA
    Nominal current I<sub>N</sub>: 5 A (25°C)
    Nominal discharge surge current I<sub>n</sub> (8/20) µs (Core-Earth): 50 kA
    Nominal discharge surge current I<sub>n</sub> (8/20) µs (Core-Shield): 50 kA
    Output voltage limitation at 1 kV/µs (Core-Earth) spike: ? 12 V (6 kV/3 kA)
    Output voltage limitation at 1 kV/µs (Core-Earth) static: ? 12 V (6 kV/3 kA)
    Output voltage limitation at 1 kV/µs (Core-Shield) spike: ? 12 V (6 kV/3 kA)
    Output voltage limitation at 1 kV/µs (Core-Shield) static: ? 12 V (6 kV/3 kA)
    Permissible HF power P<sub>max.</sub> at SWR=xx (50 Ohm system): ? 500 W
    Permissible HF power P<sub>max.</sub> at SWR=xx (50 Ohm system): ? 4 kW (peak)
    Protection level U<sub>P</sub> (Core-Earth): ? 12 V (6 kV/3 kA)
    Protection level U<sub>P</sub> (Core-Shield): ? 12 V (6 kV/3 kA)
    Standing wave ratio SWR in a 50 ? system: Typ. 1.1 (? 1.20 (0.82 GHz...2.2 GHz))
    Surge carrying capacity in acc. with IEC 61643-21 (Core-Earth): C2 (10 kV/5 kA)
    Surge carrying capacity in acc. with IEC 61643-21 (Core-Earth): D1 (2.5 kA)
    Surge carrying capacity in acc. with IEC 61643-21 (Core-Shield): C2 (10 kV/5 kA)
    Surge carrying capacity in acc. with IEC 61643-21 (Core-Shield): D1 (2.5 kA)
    Total surge current (8/20) µs: 60 kA
    VDE requirement class: C2
    VDE requirement class: C3
    VDE requirement class: D1