Menu

2762100 - Phoenix Contact Surge Protection Device

Type 3 surge protection device Rail-mountable module with surge voltage equipment protection for 3-phase power supply units, optical power and fault display, mounting on NS 35/7.5. Nominal voltage: 230 V AC/DC, housing width: 75 mm


Part #: 2762100
$285.69Order Details
Availability :
Backordered

Phoenix Contact Surge Protection Device

Color: Black
Material: PA
Connecting Thread: M3
Type: 3, Rail-Mountable Module
Nominal Current: 3x 16 A
Connection: Screw Connection
Positions: 4
Protection Level: IP20
Nominal Voltage: 230 VAC
Product Type: Surge Protection Device
  • Non-heating apparatus connection, power supply
    Conductor cross section AWG/kcmil max: 12
    Conductor cross section AWG/kcmil min.: 24
    Conductor cross section solid max.: 4 mm²
    Conductor cross section solid min.: 0.2 mm²
    Conductor cross section stranded max.: 2.5 mm²
    Conductor cross section stranded min.: 0.2 mm²
    Connection method: Screw connection
    Connection type IN: Screw terminal blocks
    Connection type OUT: Screw terminal blocks
    Screw thread: M3
    Stripping length: 8 mm
    Tightening torque: 0.5 Nm
  • Protective circuit
    Arrester rated voltage U<sub>C</sub> (L-PE): 250 V AC
    EN type: T3
    Ground conductor current I<sub>PE</sub>: ? 1 µA
    IEC category: III
    Max. discharge surge current Imax (8/20) µs maximum (L-N): 6.5 kA
    Max. discharge surge current Imax (8/20) µs maximum (L-PE): 6.5 kA
    Max. required back-up fuse: 16 A (gL)
    Message: Surge protection fault: Optical, remote indicator contact
    Nominal current I<sub>N</sub>: 3x 16 A (40°C)
    Nominal discharge surge current I<sub>n</sub> (8/20) µs (L-N): 2.5 kA
    Nominal discharge surge current I<sub>n</sub> (8/20) µs (L-PE): 2.5 kA
    Nominal frequency f<sub>N</sub>: 50 Hz
    Nominal frequency f<sub>N</sub>: 60 Hz
    Nominal voltage U<sub>N</sub>: 230 V AC (up to 400 V)
    Operating effective current I<sub>C</sub> at U<sub>C</sub>: ? 1 mA
    Protection level U<sub>P</sub> (L-N): ? 1.3 kV (2.5 kA (8/20 µs))
    Protection level U<sub>P</sub> (L-PE): ? 1.5 kV (4 kV (1.2/50) µs)
    Response time tA (L-N): ? 25 ns
    Response time tA (L-PE): ? 100 ns
  • Remote indicator contact
    Connection name: Remote fault indicator contact
    Max. operating current I<sub>max</sub>: 1 A
    Maximum operating voltage U<sub>max.</sub> AC: 250 V AC
    Switching function: N/C contact
  • Standards
    Ambient temperature (operation): -25 °C ... 75 °C
    Color: black
    Degree of protection: IP20
    Depth: 63 mm
    Design: Rail-mountable module, one-piece
    Direction of action: 3L-N & N-PE
    Height: 77.5 mm
    Housing material: PA
    Inflammability class according to UL 94: V0
    Mounting type: DIN rail: 35 mm
    Number of positions: 4
    Standard - Electrical safety: IEC 61643
    Standard - Electrical safety: E DIN VDE 0675-6
    Width: 75 mm